1
|
Do not install with the discharge side facing downward.
|

|
|
2
|
Do not install with the discharge side facing downward.
|

|
|
3
|
SL-SN, SH types must not be installed in a leaning position.
|

|
|
4
|
The check valve must not be exposed to any deflected flow directly after
the pump or other valve.
|

|
|
5
|
If air is trapped in the pipe before the check valve, chattering may occur
when starting pump operation. Make sure to install an exhaust valve in
such cases.
|

|
|
6
|
If the check valve on a submerged or vertical pump is installed at ground
level, the inlet side of the check valve may become a vacuum when the pump
is stopped and may cause water hammer. Carefully plan the location of the
check valve in such cases.
|

|
|
7
|
In addition to water hammer directly after the discharge of the pump, examine
surging due to negative pressure in the middle of piping. (Please contact
us for details.)
|

|