| Non-Water Hammer Check Valve SL series (PAT.)
|
| |||||||
Technical data Solution to water hammer caused by simple reverse flow Solution to water hammer caused by recombined flow after water column separation 1 Do not install with the discharge side facing downward. 2 Do not install with the discharge side facing downward. 3 SL-SN, SH types must not be installed in a leaning position. 4 The check valve must not be exposed to any deflected flow directly after the pump or other valve. 5 If air is trapped in the pipe before the check valve, chattering may occur when starting pump operation. Make sure to install an exhaust valve in such cases. 6 If the check valve on a submerged or vertical pump is installed at ground level, the inlet side of the check valve may become a vacuum when the pump is stopped and may cause water hammer. Carefully plan the location of the check valve in such cases. 7 In addition to water hammer directly after the discharge of the pump, examine surging due to negative pressure in the middle of piping. (Please contact us for details.) | |||||||||||||||||||||||||||||||||||||||||
|
| ||||||||||||||||||||||||||||||||||||||||